MIDAS-X-COS | Honeywell Midas® carbonyl sulfide ppm COS
MIDAS-X-COS is a Honeywell Midas® IR cartridge for carbonyl sulfide (COS), range ppm COS, IR. It plugs into the MIDAS-T-004 extractive transmitter — not a Sensepoint XCD diffusion head. Sample line up to 30 m FEP at ~500 mL/min.

Mechanical & wiring figures




Nyahkod nombor bahagian
| Segmen | Maksud | SKU ini |
|---|---|---|
| MIDAS | Honeywell Midas® extractive | MIDAS |
| COS | carbonyl sulfide | COS |
Spesifikasi
| Category | Kartrij IR |
|---|---|
| Gas | COS / carbonyl sulfide |
| Range | ppm COS |
| Principle | IR |
| Flow | approx. 500 mL/min |
| Sample length | 2–30 m FEP |
| Supply | 24 VDC or PoE 48 V |
| Outputs | 0–21 mA + 3 relays + Modbus TCP/PoE |
| Temperature | 0–40 °C (0–30 °C with pyrolyzer) |
| Size / mass | 150×65×153 mm / 0.8 kg |
| Approvals | CE, EN 50270, UL 61010-1, IEEE 802.3af |
Transmitter 150×65×153 mm / 0.8 kg; NF₃ pyrolyzer 70×63×85 mm / 0.41 kg; high-temp PFC pyrolyzer 100×101×140 mm / 1.36 kg.
Mengapa SKU ini
Midas is extractive: the cell sits in the tool cabinet while FEP pulls sample from the valve box. carbonyl sulfide uses IR. Pyrolyzed species need MIDAS-T-00P / T-HTP / T-NP1 or the cartridge will not read.
Pasangan dan alat ganti
MIDAS-X-COS mates to MIDAS-T-004. Pump MIDAS-A-007, internal filter MIDAS-A-009. Do not substitute an electrochemical cartridge for this IR cell. Calibration notes live on product-2679.
Aplikasi biasa
Gas cabinets, VMBs, wet benches and CVD/etch exhaust. MIDAS-X-COS locks gas and cartridge life; budget transmitter, pump A-007 and internal filter A-009 on the PM cycle.
Banding
| P/N | Type | Gas | Range |
|---|---|---|---|
| MIDAS-T-004 | Pemancar ekstraktif | MIDAS-T-004 | — |
| MIDAS-I-CO2 | Kartrij IR | CO₂ | 0–2.0 %vol |
| MIDAS-I-SF6 | Kartrij IR | SF₆ | ppm SF₆ |
| MIDAS S2-I-CH2 | Kartrij IR | CH₂F₂ | ppm CH₂F₂ |
| MIDAS S2-I-CH3 | Kartrij IR | CH₃F | ppm CH₃F |
| MIDAS S2-I-CO2 | Kartrij IR | CO₂ | 0–2.0 %vol |
| MIDAS S2-I-SF6 | Kartrij IR | SF₆ | ppm SF₆ |
Pemasangan dan talian sampel
Wall-mount MIDAS-T-004 on the pre-drilled chassis or DIN kit A-036, then insert MIDAS-X-COS. Sample 1/8″ID×1/4″OD FEP to 30 m; exhaust 1/4″ID×3/8″OD to 30 m. End-of-line filter 0780248 or 1830-0055/0027 by gas. 24 VDC (−15%/+10%) or PoE 48 V; pyrolyzer load up to 12.95 W. 0–40 °C, 0–30 °C with pyrolyzer.
Soalan lazim
- Can MIDAS-X-COS plug into Sensepoint XCD?
- No. Midas is an extractive cartridge; XCD is a diffusion sensor housing. They do not mate.
- Does MIDAS-X-COS need a pyrolyzer?
- Gases marked ** (CH₂F₂, C₄F₆, C₅F₈, NF₃, CH₃F) need MIDAS-T-00P / T-HTP / T-NP1 plus a ventilated cover.
- How is 4–20 mA landed on MIDAS-X-COS?
- 3-wire sink, 3-wire source or 4-wire isolated 0–21 mA; plus 3 relays and Modbus TCP / PoE. Max 14 AWG.
Dokumen
Datasheet PDF · Chinese manual · English technical manual · Matriks keluarga Midas
Sebut harga
Stok mengikut batch. Jika kartrij E habis, lihat kartrij S gas yang sama. Gas pirolisis mesti dipesan bersama modul pirolisis.