Honeywell XNX XNX-AMAV-NNIC1 – MPD IR carbon dioxide 0–5 %v/v, mV, ATEX, Aluminium, M25
XNX-AMAV-NNIC1 is a factory-configured Honeywell XNX with MPD infrared carbon dioxide 0–5 %v/v, mV personality, ATEX / IECEx (INMETRO on selected MPD SKUs), 4 × M25, LM25 aluminium (painted), 4–20 mA HART only (no option board), no local HART port. Use it on beverage carbonation, inerting cabinets and fermenter headspace—not as a toxic ppm cell.
Same sensor, swap enclosure/approval: aluminium XNX-AMAV-NNIC1, 316SS XNX-AMSV-NNIC1, other approval XNX-UTAV-NNIC1. XNX-AMAV-NNIC1 · XNX-AMSV-NNIC1 · XNX-UTAV-NNIC1

Part-number decode
| Segment | Meaning | This SKU |
|---|---|---|
| XNX | Honeywell XNX universal transmitter | XNX |
| A / U | Approval A=ATEX/IECEx; U=UL/cUL | A |
| M / T | Entry M=M25; T=3/4" NPT | M |
| A / S | Enclosure A=aluminium; S=316SS | A |
| V / I / E | Personality V=mV(MPD); I=IR Optima/Excel; E=EC | V |
| N / R / M / F | Option N=HART only; R=relays; M=Modbus; F=FFB | N |
| N / H | Local HART port N=no; H=yes | N |
| IC1 | MPD IR carbon dioxide 0–5 %v/v | IC1 |
Same sensor, swap enclosure/approval: aluminium XNX-AMAV-NNIC1, 316SS XNX-AMSV-NNIC1, other approval XNX-UTAV-NNIC1.
Technical specifications
| Category | Transmitter Configured |
|---|---|
| Personality | mV personality (MPD catalytic / MPD IR) |
| Sensor / range | MPD IR carbon dioxide 0–5 %v/v |
| Target | CO₂ / carbon dioxide |
| Principle | MPD infrared (CO₂) |
| Output | 4–20 mA HART only (no option board) |
| Local HART | no local HART port |
| Supply | 16–32 VDC (24 VDC nominal) |
| Enclosure | LM25 aluminium (painted) |
| Entries | 4 × M25 |
| Display | Backlit LCD, magnetic-wand menus |
| Ingress | IP66 |
| Approvals | ATEX / IECEx (INMETRO on selected MPD SKUs) |
| Temperature | −40~+65 ℃ |
| Mass | approx. 2.8 kg |
| Mates with | Honeywell MPD catalytic bead or MPD infrared sensors |
Why this personality / sensor
CO₂ is heavier than air and fills cellars from the floor up. Percent-level CO₂ is an IR measurement; an electrochemical toxic cell cannot span 5 %vol. Mount 300 mm above the lowest floor and keep the optical path off wet drains.
Personality and replaceable parts
XNX-AMAV-NNIC1 uses the mV personality (MPD catalytic / MPD IR) board and mates with Honeywell MPD catalytic bead or MPD infrared sensors. Factory-fitted with MPD IR carbon dioxide 0–5 %v/v. Spares live on product-3991. Do not substitute Sensepoint XCD cartridges on XNX.
Typical applications
Soft-drink carbonation, brewery cellars and CO₂-inerted cabinets need a 5 %vol trip before asphyxiation. XNX provides the hard-wired extract start; a portable wand is only a leak survey tool.
Selection contrast
| P/N | Gas | Range | Option | Body |
|---|---|---|---|---|
| XNX-AMSV-NNIC1 | CO₂ | 0–5 %v/v | HART | 316SS |
| XNX-UTAV-NNIC1 | CO₂ | 0–5 %v/v | HART | Aluminium |
| XNX-AMAV-NNCB1 | LEL | 0–100 %LEL | HART | Aluminium |
| XNX-AMAV-NNIV1 | CH₄ | 0–100 %LEL | HART | Aluminium |
| XNX-AMAV-NNIF1 | C₃H₈ | 0–100 %LEL | HART | Aluminium |
| XNX-AMAV-NNNNN | body | — | HART | Aluminium |
| XNX-AMAV-RNIC1 | CO₂ | 0–5 %v/v | Relays | Aluminium |
Installation and wiring
Wall-mount XNX-AMAV-NNIC1 (LM25 aluminium (painted), approx. 2.8 kg) on a rigid stand sized for that mass. This SKU uses 4 × M25 entries—glands must match; do not retap XNX-AMAV-NNIC1. Land XNX-AMAV-NNIC1 4–20 mA HART per the loop drawing; relays/Modbus/FFB exist only on the matching option board. Magnetic-wand menus on the XNX-AMAV-NNIC1 lid stay non-intrusive. XNX-AMAV-NNIC1 5 %v/v CO₂ hugs the cellar floor.
FAQ
- Is XNX-AMAV-NNIC1 a toxic ppm CO₂ detector?
- No. XNX-AMAV-NNIC1 is 0–5 %v/v IR for asphyxiation / inerting. ppm indoor-air CO₂ is a different instrument class.
- Should I mount XNX-AMAV-NNIC1 high or low?
- Low. CO₂ is heavier than air. Keep XNX-AMAV-NNIC1 about 300 mm above the lowest floor, not at the roof ridge.
- When should I swap XNX-AMAV-NNIC1 aluminium for 316SS?
- Use XNX-AMAV-NNIC1 (aluminium, ~2.8 kg) in inland, painted plant. Coastal, splash and sour-water decks should move to stainless sibling XNX-AMSV-NNIC1.
- Can I convert XNX-AMAV-NNIC1 from ATEX M25 to NPT in the field?
- No. XNX-AMAV-NNIC1 flameproof entries are machined M25. North-American NPT is UL sibling XNX-UTAV-NNIC1, not an adaptor on this ATEX body.
- Does XNX-AMAV-NNIC1 include alarm relays?
- No. XNX-AMAV-NNIC1 is 4–20 mA HART only. Local trip contacts need option-R sibling XNX-AMAV-RNIC1; plant-bus needs Modbus XNX-AMAV-MNIC1 or Foundation Fieldbus XNX-AMAV-FNIC1.
Documents
Honeywell XNX datasheet / manual · On-site XNX selection matrix
Availability and enquiry
Stock is lot-based. If this box is out, jump to 316SS XNX-AMSV-NNIC1 or UL XNX-UTAV-NNIC1 rather than a dead SKU.